UPS Installation Environments and Power Protection

>Back to Blog Site<

These UPS Installation Environment and Power Protection guidelines are provided for Riello Uninterruptible Power Supplies and power protection systems. They cover both floor standing and 19" rack mount UPS.

The UPS Environment

Temperature

Riello UPS systems are designed to operate at a constant ambient temperature of up to 40ºC without the need to de-rate them. For optimum battery life it is recommended that the ambient around the UPS should be 20ºC. If the ambient temperature exceeds this recommendation the batteries will not perform to their design life expectations.

For example if a 5 year design life battery if subjected to a constant operating temperature of 30ºC then the batteries design life will typically reduce by 50%. This reaction to temperature is not linear (e.g. at 40ºC the battery design life will be reduced to 20%). Therefore it is recommended that the UPS system is installed in an environment where the ambient temperature is controlled and monitored to 20ºC.

Humidity

The maximum humidity the UPS is subjected to must not exceed 90% (non condensing).

Altitude

If the UPS is installed at an altitude greater than 1000m Above Sea Level (ASL) we recommend that the UPS output power rating be de-rated by 1% for every 100m above 1000m. The recommended maximum height installation is 4000m ASL.

Positioning

Ventilation

Access

Visual indications

  Positioning

Related pages:

Jason Yates
Technical Manager

© Riello UPS Ltd. All rights reserved. navigation go top UPS Installation Environment Power Protection >Back to Blog Site<